Industrial DEF experts, we provide custom and pre-engineered DEF solutions for commercial and industrial application. Our insulated DEF tanks work in extreme cold or hot environments and are able to be moved, upgraded, and optimized for your operations at any time. With built in DEF dispensing, our turnkey modules are perfect for any application.
The Fireball DEF-1000 Line is an upgradeable series of modules for Diesel Exhaust Fluid (DEF) at a mine site. The module includes a drip tray sump sensor, low temperature and low tank level warnings. The DEF is stored in totes or tanks, an SS pump delivers the fluid through a very high quality filter, and then it is delivered to a variety of hose reels.
These reels can be inside the module and accessed through a small doorway or they can be located remotely. The remote reels can be in a separate heated building or in weatherproof dispenser. Each hose reel can be equipped with a meter and solenoid to allow the dispensing to be controlled by any fluid management system. We recommend the AdaptFMS system by FluidIntel.
It is expected that DEF consumption will increase over the next few years. To accommodate this, the storage and dispensing options can be reconfigured while keeping the same base unit. Each module can provide low flow dispensing at 25 LPM (6.6 GPM) for service trucks and auxiliary equipment. It can also provide high-flow dispensing at 100 LPM (26 GPM) for heavy haul trucks. The module is housed inside a standard 10 ft ISO shipping container with R20 insulation and a heater for cold climates.
The modules are constructed to PEI/RP1100- 15 requirements for DEF handling. A 1.5” Finish Thompson magnetic drive centrifugal pump is used because it has no rotating seals to leak. Cleanliness is critical to protect the costly Selective Catalytic Reduction (SCR) equipment. A stainless steel filter vessel houses 1 micron filter elements. This ensures the DEF meets the ISO 22241-1 purity level.
Our DEF tanks come with highly sophisticating filtering systems to prevent contamination and keep your equipment operating effectively.
With our bulk def storage capacity ranging from 1000 litres and above, storage ability will never be an issue. Our modules are also easily upgraded to meet your demands. If you only need 1000 litres of capacity today and 60,000 litres in the future, no problem. We can do all the heavy lifting for you and add an external storage tank to our def dispensing skid.
Diesel exhaust fluid has a high tendency to seep through small openings and crystalize once it reaches open air. Connections with elastomeric seals should be used where possible. If threaded connections cannot be avoided then a special thread sealant should be used.
Magnetic drive pumps are preferable because they do not use dynamic seals which will slowly leak and accumulate crystallization. Since some leakage and crystallization will still be inevitable, equipment connections should be rinsed with deionized or distilled water as part of the preventative maintenance routine.
Fireball Equipment Ltd.
16815 117 Avenue NW, Unit #110,
Edmonton, AB T5M 3V6
Phone: (780) 944-4819
Fax: (780) 944-4898
Email: info@fireball.ca
For Parts And Service
Edmonton: (780) 944-4819
Calgary: (403) 776-0605
Saskatoon: (306) 717-2125
Regina: (306) 216-6534
Vancouver: (236) 259-1883
Winnipeg: (204) 500-0797
Mississauga: (437) 253-4400